MachineCalcs

Electrical Box Fill Calculator

Check outlet, switch and junction box fill from conductor counts, AWG volume allowances, equipment grounds, device yokes, internal clamps and support fittings.

Electrical 14 inputs 9 results

Calculator

Usable volume marked on the box, extension ring or box assembly.
in³
Use extra groups when the box contains different AWG sizes.
Volume allowance for insulated conductors in the primary group.
Count insulated conductors that enter the box and are spliced, terminated or pass through as counted by the box-fill rule.
conductors
Equipment grounding conductors in the box are treated as one volume allowance using the largest grounding conductor present.
Enter zero if no equipment grounding conductors are present. Any positive count contributes one grounding-conductor allowance in this screen.
grounds
Largest conductor connected to the device yokes counted in this box.
Each device yoke counts as two conductor volume allowances of the largest conductor connected to that yoke.
yokes
Internal clamps count as one conductor allowance of the largest conductor present in this simplified screen. External clamps do not.
Support fittings are screened as one largest-conductor allowance each.
fittings

Results

Default result
Edit inputs
Required box volume(V_req)
15.75in³
Pass

Insulated groups: 4 x #12 AWG.

Also computed

Volume margin(V_margin)Pass2.25in³

Marked box volume exceeds required fill volume.

Box fill(F)Pass87.5%

Additional primary conductors(N_add)1conductors

Same-size reference using the primary conductor allowance.

Insulated conductor volume(V_cond)9in³

4 counted insulated conductors.

Grounding conductor volume(V_g)2.25in³

All equipment grounding conductors are counted as one grounding allowance in this screen.

Device yoke volume(V_yoke)4.5in³

Each device yoke is counted as two conductor allowances.

Method notes 3 notes
  • Formula: required box volume = insulated conductor allowances + equipment grounding allowance + device yoke allowances + internal clamp/support allowances.
  • This calculator uses NEC-style #18 through #6 AWG volume allowances. Conductors larger than #6 AWG, pull boxes, conduit bodies, raceway fill, ampacity adjustment and local amendments need separate checks.
  • Pigtails that originate and terminate in the same box are usually not counted; conductors entering the box and spliced, terminated or passing through generally are. Verify the adopted code text and box listing.

Electrical box fill is a volume allowance check: required volume = insulated conductor allowances + equipment grounding allowance + device yoke allowances + internal clamp/support allowances. This calculator uses NEC-style #18 through #6 AWG volume allowances, supports mixed conductor groups, counts device yokes as two allowances each, and reports required box volume, fill percent, remaining volume and max additional same-size conductors.

Continue workflow

All Electrical

How to use this calculator

  1. Enter marked box volume. Use the volume marked on the box, extension ring or box assembly.
  2. Count insulated conductors. Enter each conductor size group that enters the box and is spliced, terminated or passes through as a counted conductor.
  3. Add grounds and devices. Enter equipment grounding conductors, device yokes and the largest conductor connected to the devices.
  4. Check fittings and margin. Add internal clamps or support fittings, then compare required volume, fill percent and remaining volume.

How it works

Box fill is a volume allowance check: Vreq = Vconductors + Vgrounds + Vyokes + Vclamps + Vsupports The result is compared with the marked box volume: fill % = 100 x Vreq / Vbox

Insulated conductors use the allowance for their AWG size. Equipment grounding conductors are screened as one grounding-conductor allowance when at least one is present. Each device yoke is screened as two allowances of the selected device conductor size. Internal clamps and support fittings are screened using the largest conductor allowance present.

Use the conduit fill calculator for raceway area, the NEC electrical box fill calculator page for adopted-code search wording, the conduit bend offset calculator for route offsets, the conduit pull tension calculator for longer or bend-heavy pulls and the voltage drop calculator for long conductor runs.

Worked example

Verified against the live calculator

A box with four #12 insulated conductors, one equipment ground and one device yoke needs 4 x 2.25 = 9.00 in^3 for insulated conductors, 2.25 in^3 for grounds and 2 x 2.25 = 4.50 in^3 for the yoke. The total is 15.75 in^3. An 18.0 in^3 marked box has 2.25 in^3 remaining in this screen.

Reference data

Volume allowances used by this calculator for #18 through #6 AWG conductors.

NEC-style box fill volume allowances.
Conductor size Volume allowance (in^3)
#18 AWG 1.50
#16 AWG 1.75
#14 AWG 2.00
#12 AWG 2.25
#10 AWG 2.50
#8 AWG 3.00
#6 AWG 5.00

Source: NEC 314.16(B) style conductor volume allowances for #18 through #6 AWG. Verify against the adopted code edition and box/device listing.

Frequently asked questions

How do you calculate electrical box fill?

Add the volume allowances for counted insulated conductors, equipment grounding conductors, device yokes, internal clamps and support fittings, then compare the required volume with the marked box volume.

How are device yokes counted for box fill?

Each device yoke is screened as two conductor volume allowances of the largest conductor connected to that yoke. Verify multi-device and special-device cases against the adopted code and device listing.

Do grounds count for box fill?

Yes. In this screen, any positive number of equipment grounding conductors contributes one volume allowance using the largest grounding conductor present.

Do pigtails count in electrical box fill?

Pigtails that originate and terminate in the same box are usually not counted. Conductors entering the box and spliced, terminated or passing through generally are counted. Verify the adopted code text for the exact case.

Method & assumptions

  • Supports one, two or three insulated conductor-size groups from #18 through #6 AWG.
  • Any positive equipment grounding conductor count contributes one grounding-conductor allowance using the selected grounding conductor size.
  • Each entered device yoke contributes two allowances of the selected device conductor size.
  • Internal clamps and support fittings are screened using the largest conductor allowance present; external clamps are not counted.
  • This is a box-fill arithmetic screen only. Pull boxes, conduit bodies, conductors larger than #6 AWG, ampacity adjustment, raceway fill, device listings, local amendments and the adopted code text need separate verification.
Embed this calculator on your site free

Paste this where you want the calculator to appear. It stays in sync — same formulas, metric & imperial, light/dark — and a small credit link helps people find more tools.

Open widget

Live preview