MachineCalcs

Condensate Drain Size Calculator

Minimum condensate drain size from combined cooling tons per the IMC/UPC band table, plus the total fall the run needs at the 1/8 in/ft code-minimum slope.

HVAC 2 inputs 3 results

Calculator

Every unit draining to this line, added together (1 ton = 12,000 Btu/h ≈ 3.5 kW). A single unit uses its own capacity.
tons
Developed horizontal length of the drain from the pan connection to the termination — used only for the slope-fall figure.
ft

Results

Default result
Edit inputs
Minimum drain size(ID)
1in
Pass

1 in nominal — the band runs to 40 tons, leaving 14 tons of headroom before the next size.

Minimum internal diameter — the code floor is 3/4 in no matter how small the unit.

Also computed

Size band ceiling40tons

Required fall over run(Δh)5in

At the code-minimum 1/8 in/ft; confirm the route can actually drop this much before it terminates.

Total elevation drop at the 1/8 in/ft (≈1%) code-minimum slope — steeper is better.

Method notes 4 notes
  • Bands are the model-code minimums (IMC 2021 Table 307.2.2 / UPC Table 814.3): 3/4 in to 20 tons, 1 in to 40, 1-1/4 in to 90, 1-1/2 in to 125, 2 in to 250 — the locally adopted code governs.
  • Condensate drains never shrink: 3/4 in minimum everywhere, and no size decrease from the drain pan to the point of disposal.
  • Slope at least 1/8 in/ft (IMC 307.2.1 calls this 1-percent), support the pipe so it cannot sag into traps of its own, and trap the unit per the manufacturer.
  • Fuel-fired appliance (condensing furnace/boiler) condensate is acidic and separately regulated — neutralization and material rules differ from cooling-coil condensate.

Condensate drain sizing is a band lookup, not a formula: the IMC (Table 307.2.2) and UPC (Table 814.3) publish identical minimum internal diameters by combined cooling capacity — 3/4 in up to 20 tons, 1 in to 40, 1-1/4 in to 90, 1-1/2 in to 125 and 2 in to 250 — with a 3/4 in floor everywhere, no size decrease downstream, and at least 1/8 in/ft of slope. This calculator returns the band, the headroom to the next size, and the total fall the run needs; the locally adopted code governs.

Continue workflow

All HVAC

How to use this calculator

  1. Add up the connected capacity. Every unit draining to the line, in tons of refrigeration (1 ton = 12,000 Btu/h). A single unit uses its own capacity.
  2. Read the band. The calculator returns the minimum internal diameter and how much capacity headroom the band still has.
  3. Check the fall. Multiply the horizontal run by 1/8 in/ft — the route must be able to drop that much, continuously, with no sags.
  4. Verify against the adopted code. IMC and UPC agree on the bands, but the locally adopted edition and any amendments govern.

How it works

Condensate drain sizing is a band lookup, not a formula. The two model codes publish the same minimum internal diameters by combined cooling capacity, and they agree exactly:

≤20 tons → 3/4 in · ≤40 → 1 in · ≤90 → 1-1/4 in · ≤125 → 1-1/2 in · ≤250 → 2 in

Two rules ride along with the table: the drain is never smaller than 3/4 in anywhere, and it never decreases in size between the pan and the point of disposal. The third constraint is slope — at least 1/8 in per foot of horizontal run — which this page converts into the total fall the route has to find. Cooling capacity itself comes from the airflow & BTU load calculator, and what the coil actually condenses ties back to the coil bypass factor.

Worked example

Verified against the live calculator

Three rooftop units — 8, 8 and 10 tons — manifold into one condensate main with 40 ft of horizontal run:

26 tons → over 20, within 40 → 1 in minimum · fall = 40 ft × 1/8 in/ft = 5 in

The 1 in band carries to 40 tons, so there are 14 tons of headroom before a fourth unit would push the main to 1-1/4 in. The run needs a continuous 5 inches of drop — set the high point at the farthest pan and confirm the termination sits low enough before pipe goes in.

Frequently asked questions

What size condensate drain for a 5 ton AC unit?

3/4 inch. The first code band (IMC Table 307.2.2 / UPC Table 814.3) runs all the way to 20 tons of refrigeration, so every residential unit — 1.5, 3, 5 tons — lands on the same 3/4 in minimum, which is also the absolute code floor.

When does a condensate drain need to be 1 inch or larger?

When the combined capacity draining to the line passes 20 tons: 1 in carries to 40 tons, 1-1/4 in to 90, 1-1/2 in to 125 and 2 in to 250. In practice that means manifolded equipment — rooftop units sharing a main — not single residential systems.

What slope does a condensate drain need?

At least 1/8 inch per foot of horizontal run (IMC 307.2.1 labels it a 1-percent slope). Over 40 ft that is 5 inches of fall — worth checking the route can actually drop that much before the termination point.

Can a condensate drain reduce in size along the run?

No. The code is explicit: the drain shall not decrease in size from the drain pan connection to the place of disposal, and it is never smaller than 3/4 in internal diameter anywhere.

Method & assumptions

  • Bands are the model-code minimums — IMC 2021 Table 307.2.2 and UPC Table 814.3 publish identical values (verified against two independently published adoptions). The locally adopted code and its amendments govern.
  • Gravity drains from cooling-coil pans; pumped condensate, combination waste connections and indirect-waste rules are separate code territory.
  • Fuel-fired appliance (condensing furnace/boiler) condensate is acidic and separately regulated — neutralizer and material requirements differ.
  • Beyond 250 tons the published table ends; large plants size condensate hydraulically as an engineered design.
  • Traps, cleanouts, air gaps at termination and approved pipe materials come from the code text and the equipment manufacturer, not this screen.
Embed this calculator on your site free

Paste this where you want the calculator to appear. It stays in sync — same formulas, metric & imperial, light/dark — and a small credit link helps people find more tools.

Open widget

Live preview