MachineCalcs

Short-Circuit Current Calculator

Estimate available fault current from transformer kVA, percent impedance, X/R ratio, optional source stiffness and downstream impedance.

Electrical 11 inputs 8 results

Calculator

Three-phase uses line-to-line voltage and sqrt(3). Single-phase uses the entered voltage and loop impedance.
Infinite source ignores upstream impedance. Known source adds an upstream Thevenin impedance on this voltage base.
Transformer apparent-power rating in kVA.
kVA
Line-to-line voltage for three-phase, or the single-phase circuit voltage.
V
Nameplate transformer impedance percent.
%
Used to split transformer impedance magnitude into resistance and reactance.
Equivalent downstream resistance in milliohms. Use per-phase equivalent for three-phase, or loop equivalent for single-phase.
mOhm
Equivalent downstream reactance in milliohms. Use per-phase equivalent for three-phase, or loop equivalent for single-phase.
mOhm
Entered equipment interrupting rating or SCCR screen value for utilization comparison.
A

Results

Default result
Edit inputs
Available fault current(I_afc)
1,569A
Pass

below entered interrupting rating

at entered point

Also computed

Transformer-terminal fault current(I_term)1,569A

Infinite-bus transformer current(I_sc)1,569A

transformer only, infinite source

Transformer full-load current(I_fl)90.21A

Interrupting-rating utilization(U_aic)Pass7.131%

Fault apparent power(S_fault)1,304kVA

Total Thevenin impedance(Z_total)0.1766ohm

Method notes 3 notes
  • Three-phase current uses line-to-line voltage and sqrt(3); downstream R/X should be per-phase equivalent impedance.
  • Infinite-bus mode ignores upstream source impedance and is a conservative transformer-secondary screening assumption.
  • This is an available-fault-current worksheet only. Final interrupting rating, SCCR, current-limiting, arc-flash, OCPD selection and code/AHJ review require detailed system and equipment data.

Short-circuit current from transformer impedance starts with full-load current I_FL = kVA*1000/(phase factor*V), then transformer-only fault current I_SC = I_FL/(Z%/100). This calculator splits transformer, optional source and downstream impedance into R/X terms using X/R ratios, adds them as series impedance on the same voltage base, and reports available fault current, interrupt-rating utilization, fault kVA and total Thevenin impedance. It is not arc flash, current-limiting, SCCR, OCPD selection or code approval.

Continue workflow

All Electrical

How to use this calculator

  1. Enter transformer data. Use transformer kVA, secondary voltage, phase and nameplate percent impedance.
  2. Set X/R and source mode. Use infinite bus for a conservative transformer-only screen, or enter known upstream source fault current and X/R on the same voltage base.
  3. Add downstream impedance. Enter equivalent R and X for a feeder, bus or equipment point if the fault location is not at the transformer terminals.
  4. Check utilization. Compare available fault current with the entered interrupting rating or SCCR screen value.

How it works

A transformer short-circuit screen starts from full-load current. For three phase, I_FL = kVA x 1000 / (sqrt(3) x V_LL). For single phase, I_FL = kVA x 1000 / V. The transformer-only infinite-bus fault current is then I_SC = I_FL / (Z% / 100). For the exact transformer secondary search path, use the transformer impedance fault current calculator.

The short-circuit current calculator turns transformer impedance, optional source fault current and optional downstream feeder impedance into R/X components and adds them as series impedance on the same voltage base. Use the transformer kVA calculator when you still need source apparent power, the voltage drop calculator for normal load voltage drop, and the conduit fill calculator or conduit pull tension calculator after the physical raceway path is known.

Worked example

Verified against the live calculator

A 75 kVA, three-phase transformer at 480 V with 5.75% impedance has full-load current of about 90.2 A. Infinite-bus transformer fault current is 90.2 / 0.0575 = 1,570 A. With no upstream or downstream impedance entered, available fault current at the secondary terminals is the same value. A feeder or limited upstream source lowers the available current at the entered point.

Reference data

Use this worksheet to keep the voltage base and impedance terms explicit. All optional source and downstream impedance values must be converted to the same secondary-voltage base before the available-current result is meaningful.

Available short-circuit current worksheet.
Worksheet step Formula Use the result for
Full-load current I_FL = kVA x 1000 / (phase factor x V) Transformer load current
Transformer impedance Z_T = V / (phase factor x I_SC) Magnitude from kVA and Z%
R/X split R = Z / sqrt(1 + (X/R)^2), X = R x X/R Series impedance terms
Known source Z_source = V / (phase factor x I_source) Optional upstream Thevenin impedance
Fault point I_fault = V / (phase factor x |Z_total|) Available fault current

Source: Formula-only worksheet; transformer nameplate impedance, utility/generator source data, conductor impedance and equipment interrupting ratings must come from project or manufacturer data.

Frequently asked questions

How do I calculate transformer short-circuit current?

First find transformer full-load current: I_FL = kVA x 1000 / (phase factor x V). Then divide by percent impedance as a decimal: I_SC = I_FL / (Z% / 100).

What does infinite bus mean?

Infinite bus assumes the upstream source has no impedance, so transformer impedance is the only source limitation. It is a conservative first-pass transformer-secondary screen when utility or generator fault data is not known.

How do I include known source fault current?

Choose known source fault current and enter the upstream source current converted to the same secondary-voltage base. The calculator converts that current to a Thevenin impedance and adds it in series with transformer impedance.

How do I include a downstream feeder or bus run?

Enter equivalent downstream resistance and reactance in milliohms. For three-phase faults use per-phase equivalent impedance; for single-phase faults use the circuit loop equivalent.

Does this handle NEC 110.24, interrupting rating or SCCR?

It supports the available-fault-current worksheet step, but it does not approve NEC marking, interrupting ratings, equipment SCCR, current-limiting protection or installation code compliance. Use qualified electrical study data, listed equipment instructions and AHJ review for final work.

Is this an arc-flash calculator?

No. Available fault current is one input to many electrical studies, but arc-flash incident energy also needs clearing time, equipment type, enclosure data, working distance and a current standard/method.

Method & assumptions

  • Three-phase mode uses line-to-line voltage and balanced three-phase fault-current relationships.
  • Single-phase mode uses the entered voltage and loop-equivalent impedance.
  • Known-source mode assumes source fault current has been converted to the secondary-voltage base before transformer impedance is added.
  • Downstream R/X inputs are equivalent impedance values, not conductor-size or conduit lookup tables.
  • Does not calculate arc flash, breaker/fuse clearing time, current limitation, equipment SCCR, series ratings, selective coordination, DC fault current or permit/code approval.
Embed this calculator on your site free

Paste this where you want the calculator to appear. It stays in sync — same formulas, metric & imperial, light/dark — and a small credit link helps people find more tools.

Open widget

Live preview