MachineCalcs

Motor Feeder Sizing Calculator

Feeder conductor ampacity for several motors per NEC 430.24 — 125% of the largest motor FLC plus the rest, plus non-motor loads — and the 430.62(A) maximum feeder OCPD. Table-free: you enter the adopted-code FLC values. Free, no signup.

Electrical 5 inputs 3 results

Calculator

Full-load current of the HIGHEST-rated motor, from your adopted code's Table 430.250/248 (not the nameplate). 34 A ≈ 25 hp at 460 V three-phase.
A
Table FLCs of every other motor on the feeder, added together. 14 + 7.6 = 21.6 A ≈ 10 hp + 5 hp at 460 V.
A
Non-motor load expected to run 3 hours or more — counted at 125%.
A
Other non-motor load — counted at 100%.
A
Rating of the largest motor's branch-circuit short-circuit device from your 430.52 sizing. 0 skips the feeder-OCPD output.
A

Results

Default result
Edit inputs
Minimum feeder ampacity(I_min)
64.1A
Pass

The 430.24 floor — take it to your adopted ampacity table with its correction factors.

Also computed

Motor portion64.1A

1.25 × largest + the rest, before non-motor loads.

Max feeder OCPD (430.62(A))Pass111.6A

Round DOWN to a standard rating.

Largest branch device + other motors' FLC — round DOWN to a standard 240.6(A) rating.

Method notes 4 notes
  • 430.24 structure: 125% of the largest motor FLC + the sum of the other motors' FLCs + 125% of continuous and 100% of noncontinuous non-motor load. FLC values are the adopted code's table values (430.250/248), not nameplates — you enter them; nothing is embedded here.
  • The 430.62(A) ceiling rounds DOWN to a standard 240.6(A) rating — the next-size-up allowance belongs to 430.52 branch protection, not feeders.
  • Duty-cycle motors (430.22(E)), interlocked motors that cannot run together, and adjustable-speed-drive rules modify the sum — those exceptions are engineering calls outside this screen.
  • The minimum ampacity goes to your adopted ampacity table with its ambient and conductor-count correction factors (the ampacity derating calculator runs that step).

A feeder serving several motors is sized for the moment its largest motor starts while the rest run at load: NEC 430.24 requires conductor ampacity of at least 125% of the largest motor's table FLC plus the full-load currents of all the other motors, plus 125% of continuous and 100% of noncontinuous non-motor load. Three motors of 25, 10 and 5 hp at 460 V need 34 × 1.25 + 14 + 7.6 = 64.1 A. This calculator runs that structure plus the 430.62(A) maximum feeder OCPD (largest branch device + other FLCs, rounded DOWN to a standard rating) — and embeds no tables: every current comes from your adopted code.

Continue workflow

All Electrical

How to use this calculator

  1. Pull the table FLCs. Adopted-code Table 430.250/248 values for every motor — nameplates are for overloads, not feeders.
  2. Enter largest and the rest. The highest-rated motor's FLC alone, then the sum of all the others; add any non-motor load split continuous/noncontinuous.
  3. Take the floor to the ampacity table. The minimum ampacity meets your adopted table with its ambient and bundling corrections — the derating calculator runs that step.
  4. Cap the feeder device. Largest branch device + other FLCs, rounded DOWN to a standard rating.

How it works

A motor feeder is sized for the day the biggest motor starts while everything else is already running — one inrush on top of steady load. That single idea is the whole rule:

I_min = 1.25·I_largest + ΣI_others + 1.25·I_cont + I_noncont · OCPD_max = OCPD_largest + ΣI_others (round down)

Both rules run on your adopted code's table values — nothing is embedded here. Each motor's own branch circuit comes first (FLA from the motor FLA calculator, overloads from the overload size calculator), the feeder's real-world ampacity passes through the ampacity derating calculator, and the run's voltage drop through the voltage drop calculator.

Worked example

Verified against the live calculator

Three motors at 460 V three-phase — 25 hp (34 A), 10 hp (14 A), 5 hp (7.6 A) — the largest on a 90 A branch breaker:

I_min = 34 × 1.25 + (14 + 7.6) = 64.1 A · OCPD_max = 90 + 21.6 = 111.6 → 110 A standard

The 64.1 A floor goes to the adopted ampacity table with its correction factors, and the feeder device lands on 110 A — rounded down, because the next-size-up allowance belongs to branch circuits under 430.52, not to feeders. Note the asymmetry doing the work: only the 25 hp motor carries the 125%; the other two count at face value.

Frequently asked questions

How do you size a feeder for multiple motors?

NEC 430.24: feeder ampacity ≥ 125% of the largest motor's table FLC plus the full-load currents of all the other motors — plus 125% of any continuous and 100% of any noncontinuous non-motor load. Three motors of 25, 10 and 5 hp at 460 V (34, 14 and 7.6 A) need 34 × 1.25 + 14 + 7.6 = 64.1 A.

Why only 125% on the largest motor and not on all of them?

The conductor heating case the rule guards is the largest motor starting while the rest run at load — one motor's inrush at a time. Adding 25% to every motor would size for all of them starting simultaneously, which belongs to engineered soft-start/sequencing design, not the code floor.

How big can the feeder breaker be for a motor group?

430.62(A): no larger than the largest branch-circuit device rating plus the other motors' full-load currents — and that result rounds DOWN to a standard 240.6(A) rating. With a 90 A branch breaker on the 25 hp motor, 90 + 21.6 = 111.6 A → a 110 A feeder device. The round-UP allowance people remember is 430.52's, for branch circuits only.

Do I use nameplate amps or table values?

Table values — your adopted code's Table 430.250 (three-phase) or 430.248 (single-phase) — for both 430.24 and 430.62 feeder math. Nameplate FLA is for overload protection (430.32). This calculator embeds no tables: you enter the values from the edition your jurisdiction adopts.

Method & assumptions

  • NEC 430.24 / 430.62(A) rule structure (verified 2026-06-11 against agreeing published walkthroughs); the adopted edition and the AHJ govern. No FLC, ampacity or protection-percentage tables are embedded — every current is yours from the adopted code.
  • Duty-cycle motors (430.22(E)), interlocked motors that cannot run simultaneously, and adjustable-speed-drive input ratings modify the sums — engineering judgments outside this screen.
  • The OCPD ceiling shown is the motors-only 430.62(A) case; feeders that also carry non-motor load follow 430.62(B)/430.63 for protection (flagged in the result when applicable).
  • Power-factor correction, transformer in the feeder path and service-level rules bring their own articles.
Embed this calculator on your site free

Paste this where you want the calculator to appear. It stays in sync — same formulas, metric & imperial, light/dark — and a small credit link helps people find more tools.

Open widget

Live preview