Transformer kVA Calculator

Single-phase uses V x I / 1000. Three-phase uses sqrt(3) x line-to-line voltage x line current / 1000.
Calculate from volts and amps, or from real power and power factor.
Line-to-line voltage for three-phase loads, or winding/load voltage for single-phase.
V
Line current in amperes.
A
Used to convert kW to kVA and to estimate real kW when amps are entered.
Extra capacity before rounding to the next listed standard size.
%

Results

Default result
Edit inputs
Recommended standard size (S_std)
75 kVA
Pass

next listed three-phase size

Also computed

Design kVA with margin (S_design) 62.35 kVA

Load kVA (S_load) 49.88 kVA

Standard-size full-load current (I_fl) 90.21 A

Load current (I_load) 60 A

Standard-size utilization (U) Pass 66.51 %

Spare capacity vs load (S_spare) 25.12 kVA

Method notes 2 notes
  • Three-phase kVA uses sqrt(3) x line-to-line volts x line current / 1000.
  • This is a transformer apparent-power screen. Final selection still needs continuous-load rules, inrush, motor starting, harmonic heating, impedance, enclosure, temperature rise, primary/secondary protection and local code review.