Use one group for same-size conductors, or add second/third groups for mixed wire sizes.
Conductor insulation type and size. Fill uses the outside area of the insulated conductor, not bare copper area.
Count each conductor occupying conduit area. Mixed sizes should be summed separately; this calculator screens same-size conductors.
Second conductor size for mixed raceway fill.
Count of the second conductor size. Set to 0 to ignore this group.
Third conductor size for mixed raceway fill.
Count of the third conductor size. Set to 0 to ignore this group.
Conduit type and trade size. Use the exact internal area for the raceway actually being installed.
Standard raceway fill uses conductor-count limits. Short nipples can use the 60% screen when the code condition applies.
3/4 EMT (0.533 in²) passes for 9 conductors.
Also computed
three-or-more conductor rule
if all conductors are #12 THHN/THWN-2